Primary Voltage Ratings: 115 kV
Secondary Voltage Ratings: 13.8 kV
TYPE: Three Phase LTC Transformer
Standards: IEEE C57.12.00
Power Rating: 30 / 40 / 50 MVA
Cooling Type: ONAN / ONAF 1 / ONAF 2
This transformer is a 3 phase LTC type electrical transformer designed and developed for Oklahoma USA. The transformer will be a part of the national grid and electricity supply system of the USA and thus comply with all the international standards that are being followed in the USA including IEEE standards.
The transformer is designed to operate at 60 Hz frequency, 35 degree ambient temperature and at the altitude of about 3300 feet above the sea level. The transformer is designed to offer multiple power ratings to match the ongoing grid station power rating. The transformer also offers multiple cooling systems to match with the ongoing power rating. This transformer is designed with the vector group Dyn1.
| Field | Value |
| Type | Three Phase LTC Transformer |
| Operating Frequency | 60 Hz |
| Tap | LTC |
| Tap Position | 17 Positions |
| Power Rating | 30 / 40 / 50 MVA |
| Operating Altitude | 3300 feet |
| Base Power | 30 MVA |
| Rated Voltage | 115 kV |
| HV BIL | 550 kV |
| LV BIL | 110 kV |
| Cooling Mechanism | ONAN / ONAF 1 / ONAF 2 |
| Vector Group | Dyn1 |
| Construction Type | Core |
| Ambient Temperature | 35 C |
| Design SEISMIC Capacity | Low per IEEE 693-2005 |
| Manufacturing Standard | IEEE C57.12.00 |
| Overload Rating OF OLTC | IEEE C57.131 |
| Total Weight | 149600 lb |
Contact Daelim Transformer for special requirements
Following are the some key features of this electrical transformer that is designed and developed for Oklahoma USA as per the client and application requirement.
As this transformer will be part of the Oklahoma electricity system and installation can be in either electricity generating power plant or in the national grid for distribution purpose. For this reason, the transformer is designed to offer three different power ratings.
The transformer offer
In the above mentioned power ratings, the power rating of 30 MVA acts as the base power rating of the transformer and all other calculations like impedance, no load power losses, and load power losses are calculated based on this power rating.
Three different power ratings are not enough for complete integration of the transformer with the national grid station. This transformer is designed to work on a very wide range of voltages and current rating for each of the transformer power ratings. This ensures true integration of transformers in the national grid system in each and every situation.
The transformer is designed to offer 17 different combinations of electrical voltages and current for any given power rating at its high voltage winding side. The high voltage winding side of the transformer is designed with delta configuration.
The low voltage winding side is designed to operate on single voltage for each of the power ratings with appropriate current rating. The low voltage winding side of the transformer is designed with wye grounded configuration.
| Winding | Voltage KV | Configuration | Current Amps | ||
| 30 MVA | 40 MVA | 50 MVA | |||
| HV | 126.5 to 103.5 | Delta | 136.9 to 167.3 | 182.6 to 223.1 | 228.2 to 278.9 |
| LV | 13.8 | Wye grounded | 1255.1 | 1673.5 | 2091.8 |
The transformer is provided with a load tap changer that enables the operator to change the tap position and get the required combination of voltage and current for the given power rating with the transformer being fully energized.
The 17 different combinations of voltage and current are achieved through 17 different tap positions of this transformer. The base line position of the tap changes what we called the base voltage and current setting and for a base power rating of 30 MVA it is 115000 V with 150.6 amps of current. From this base line we have 8 different tap positions for higher voltage where you can select a high voltage up to 126500 volts. Similarly we have 8 different tap positions for lower voltage where you can select a high voltage up to 103500 volts.

The LTC transformer with three different power ratings is provided with three different cooling systems to compensate for the extra waste heat being generated at higher power. The transformer has
The oil natural air natural cooling system is for 30 MVA power rating when minimal waste heat is being produced at the winding section. The oil natural air force cooling system no 1 is for 40 MVA power rating when waste heat needs to be removed by force.
Similarly the oil natural air force cooling system no 2 is for 50 MVA power rating when maximum waste heat is being produced and needs to be removed by both air forced cooling systems. To support the cooling of the transformer, the transformer also has a removable radiator to support the forced air cooling system with fins and extra oil in the fins.
The transformer contains 5502 gallons of mineral oil in the tank, 644 gallons of mineral oil in the radiator, 80 gallons of mineral oil in LTC and 288 gallons of mineral oil in con.
Each part of the transformer like tank, fitting, oil, radiator and other parts have their fair share in total weight of the transformer. It is important to fully understand the weight of a transformer as it is one of the main factors during transportation and installation.
| Component | Weight (lbs) / Volume |
| Core and Coils | 70400 |
| Tank and Fittings | 35420 |
| Removable Radiator | 4807 |
| At 25 C 5502 Gal of mineral oil in Tank | 41094 |
| At 25 C 644 Gal of mineral oil in rads | 4806 |
| At 25 C 80 Gal of mineral oil in L T C | 596 |
| At 25 C 288 Gal of mineral oil in Con | 2152 |
| Total Weight | 149600 |
| Weight of Transport (with oil) | 118800 |
| Rise or Fall per 10°C Temperature Change | 0.75 in |
As this transformer is for the USA, it has to comply with all regions and concern international standards. This transformer was designed, developed and commissioned by complying with the following standards.
Transformer is also featured with all types of safety features like
The 115 kV, 50 MVA power transformer weighs approximately 150 tons. To ensure safe transportation and minimize the risks associated with oversized and heavy-haul shipping, our shipping and logistics team adopted a split-shipment approach.
Before transportation, removable components, including the high-voltage and low-voltage bushings, conservator tank, and radiators, were dismantled from the transformer main tank, separately packaged, crated, and shipped.
For components that remain mounted on the transformer main tank, such as the control cabinet and tap changer operating mechanism, custom-built wooden crates were used to provide additional protection against potential impacts and vibrations during transit.
In addition, the transformer main tank was equipped with a nitrogen protection system to protect the internal insulation system during transportation. An impact recorder was also installed to monitor and record any shocks and vibrations encountered throughout the journey, providing valuable data for transportation safety monitoring and post-delivery condition assessment.
This comprehensive transportation and protection plan helps ensure the safe delivery of large power transformers throughout long-distance transportation and handling operations. Please see the following photos for details of the packaging and transportation arrangements.

Daelim Transformer is trusted globally for transformer manufacturing due to its proven track record of delivering high voltage transformers for grid integration and tailored to specific regional requirements like those of the USA. Our 115 kV 50 MVA LTC transformer designed for Oklahoma is a perfect example of our capabilities to meet complex engineering and operational requirements like different power ratings, variable voltage acceptance, IEEE standard compliance including IEEE C57.12.00, IEEE C57.131, and IEEE 693-2005.
If you have any questions about electrical transformers, Contact our team and they will be happy to help you.
Please Write your message, ask for price, we will reply you soon, thanks