40 MVA Transformer for Solar Park

Additional information

Primary Voltage Ratings: 110kV

Secondary Voltage Ratings: 20kV

CONNECTION TYPE: YNd11

TYPE: Conservator Type

BIL: 550/125kV

Standards: IEC

Application: Solar Park

Power Rating: 40MVA

Cooling Method: ONAN/ONAF

The 40 MVA transformer is utilized in a 50 MWac solar park in eastern Albania. This step-up transformer connects to the government’s 110 kV substation, with a primary voltage of 20 kV and a secondary voltage of 110 kV. It features an ONAN/ONAF cooling method and an OLTC (On-Load Tap Changer) with 17 taps adjustment positions (±8*1.5%). The transformer is designed and manufactured in accordance with IEC standards.

Contact Daelim Transformer for special requirements

CharacteristicsDataUnit
Rated Power@ONAN40 MVA
@ONAF50 MVA
Cooling methodONAN/ONAF
No Load Rated Voltages( HV/LV )110 / 20kV
Voltage Tapping@ HV17 taps; (+8 ; -8) x 1,50% On Load
Vector GroupYNd11
Frequency50 Hz
Maximum Ambient Temperature40 °C
Average Winding / Top Oil Temprature Rise Limits65 / 60
Altitude<1200m
No-Load Losses@1.0xUnPo29 kW
Load Losses@75 °C, 110/20 kV & 50 MVAPk199 kW
Short Circuit Impedance@75 °C, 110/20 kV & 50 MVAUk11 %
No-Load CurrentIo3%
No-Load Sound Pressure Level@1 m ONANLpA75 dB
Insulation LevelsBIL (kV)AC (kV)
HV550 230 
HV-N250 95 
LV125 50 
Bushing Types and Terminations
HVCondenserOpen Air
HV-NDINOpen Air
LVDINOpen Air
HV Bushing
LV Bushing
On-Load Tap Changer
Oil Temperature Indicator
Winding Temperature Indicator
Oil Level Indicator (Main Tank)
Oil Level Indicator (OLTC Conservator)
Buchholz Relay (Main Tank)
Buchholz Relay (Seperator)
Pressure Relief Device
Control Cabinet
Automatic Voltage Regulator (AVR)
Breather (Main Tank)
Breather (OLTC)
Cooling Fans
Separator
Thermal Image Current Transformer
Impact Recorder

Daelim Transformer has specialized in transformer design and production for the international market for over 20 years. Our team possesses extensive technical expertise and experience. Whether your project is located in North America, Central and South America, Europe, Australia, or other regions, we are equipped to provide reliable, safe, and competitive transformer solutions.

Scope of Power Transformer Supply

  • Standards: IEEE/ANSI, CSA, IEC, BS, AS/AZS
  • Power Rating: Up to 500 MVA
  • High Voltage: Up to 345 kV
  • Regions: North America, South America, Australia, Europe, etc.

For detailed information, please contact Daelim Transformer.

 

40MVA Transformer Manufacturing

40 mva transformer manufacturing

 

Finished Transformer In The Workshop

40mva transformer

 

40 MVA Transformer Testing

40 mva transformer testing

40 MVA Transformer Package and Shipping

40mva transformer package and shipping

Quote Now

Please Write your message, ask for price, we will reply you soon, thanks

Right Sidebar Form

Get A Quote

Contact Us