4600 kVA Inverter Duty Transformer

Additional information

Primary Voltage Ratings: 33 000 V

Secondary Voltage Ratings: 480 V

H.V. TAP RANGE: -5 % to +5 %

TYPE: Inverter Duty Transformer

Standards: AS/NZS

Application: BESS

Power Rating: 4600 kVA

Cooling Method: ONAN

The 4600 kVA Inverter Duty Transformer boasts rugged construction, high overload capability, and low noise and vibration levels. Purpose-built for energy storage applications, it excels under high-frequency and transient load conditions. Specifically tailored for the Australian market, this transformer complies meticulously with AS standards.

Rating4.6 MVA / 2.3 MVA / 2.3 MVA
Phase3
Frequency50 Hz
No. of windings 3
Nominal primary voltage33 kV
Nominal secondary voltage480 V
Nominal tertiary voltage480 V
Vector groupDyn11yn5
Impedance7.5 % )
Transformer efficiency99% (minimum)
Operating modeSingle
Location

Degree of protection

Harmonics compliance

Method of cooling

Insulation level – primary 

Power frequency withstand voltage-primary 

Lightning impulse withstand voltage – primary 

Outdoor

IP56

As per AS/NZS 

Natural Convection

36 kV (rms)

70 kV (rms)

200 kV (peak)

Contact Daelim Transformer for special requirements

Oil level low (alarm)With externally readable gauge
Oil level tripYes
Oil temperature high (alarm)With externally readable gauge
Oil Temperature tripYes
Winding temperature RTDYes
Pressure relief device Yes
Winding temperature high (alarm)With externally readable gauge
Winding temperature tripYes
Main tank Buchholz relayYes
TypeOff load tap changer at primary winding
Tapping Range-5 % to +5 %
Principal tap33,000 V
Number of tap positions5
Change per step2.5 %
Temperature (max/min)50 / 0 degC
Average Summer Dry Bulb temperature30.4 degC
Relative humidity (max/min)20 – 65 %
Maximum Design Humidity100%
Site elevation< 50 m
Proximity to the Sea10 km
Atmospheric corrosivity category C4
Wind Region D
Terrain Category 1
Pollution levelIV – Very Heavy

The 4600 kVA transformer features a low-voltage double-split structure, with its capacity divided into two equal parts of 2300 kVA each. These segments can operate independently or simultaneously, each connected to a battery pack separately.

Double-split transformers facilitate electrical isolation between the two inverters, effectively reducing electromagnetic interference and circulating current between the branches. Furthermore, they ensure that the AC outputs of the inverters are filtered individually, resulting in minimal output current harmonics and enhanced power quality.

In the event of a short circuit in one branch, the transformer not only effectively limits the short-circuit current but also maintains the voltage of the other branch at a certain level, thus ensuring uninterrupted user operations.

Hence, it is evident that double-split step-up transformers are the preferred choice for large-scale photovoltaic power generation and energy storage projects.

With extensive experience in large-scale photovoltaic power generation and energy storage projects, Daelim Transformer can meet all technical requirements associated with such projects. Additionally, our professional team can significantly save on time costs, and our fast delivery times ensure the smooth completion and delivery of projects. Contact us now to discuss your next project.