Primary Voltage Ratings: 138 kV
Secondary Voltage Ratings: 13.8 kV
TYPE: 3 Phase Power Transformer
Standards: CSA C88
Power Rating: 15/20 MVA
Cooling Type: KNAN (15 MVA) / KNAF (20 MVA)
It is a power transformer designed and developed to regulate 3 phase electricity at 60 Hz frequency for Canadian electricity generating power plants and grid stations. The transformer is designed and built to comply with CSA C88 Canadian national standards.
The transformer is designed with all the features needed for a safer, reliable, and efficient electricity regulation at a power plant or grid station. The transformer offers multiple power ratings to match incoming electrical power, multiple cooling systems to remove all the waste heat, and different tap positions to deliver different combinations of voltage and current as per the requirements of grid stations and power generating plants.
| Field | Value |
| Type | 3 Phase Power Transformer |
| Rated Capacity | 15000 kVA @ 15 MVA |
| Rated Voltage | 138 +- 2×2.5% |
| HV rated voltage | 144.9 to 131.1 kV |
| LV rated voltage | 13.8 kV |
| Rated Frequency | 60 Hz |
| Connection Category | Dyn1 |
| Technical Standards | CSA C88 |
| Insulation Level | LI650AC275 / LI110AC38 – LI110AC38 |
| Equipment Type | Outdoor |
| Altitude | < 1000 m |
| Cooling Method | KNAN (15 MVA) / KNAF (20 MVA) |
| Impedance | 8.21 % K @ 15 MVA |
| Load Losses | 48.20 KW |
| No load loss | 15.23 KW |
| No load current | 0.12 % |
| Total Weight | 83800 lb |
Contact Daelim Transformer for special requirements
The transformer is designed and built with following features that were required as per Canadian standards and client requirements.
This power transformer is designed to operate on two different power ratings but one at a time. The transformer offers 15 MVA and 20 MVA power rating so that the transformer power rating can be adjusted as per the power plant or grid station working. From the given two power ratings, 15 MVA works as the rated power rating of this power transformer and all further measurements and calculations mentioned against transformer specification are measured and calculated on this rated capacity of the power transformer.
The transformer is provided with two standard windings, a high voltage winding and low voltage winding. Both winding can be operated on both power ratings of the transformer. The high voltage winding is designed to operate on a range of electrical voltage with delta configuration. The low voltage winding as a standard practice operates on a single voltage for both of the power ratings.
| Winding | Voltage kV | Configuration |
| HV | 144.9 to 131.1 | Delta |
| LV | 13.8 | Wye (grounded) |

This power transformer is provided with a tap changer with five positions. The tap changer can change the transformer setting to adjust the high voltage winding so that it can operate on the required combination of the electrical voltage and current. Each tap position offers a unique combination of electrical voltage and current for both the transformer power rating. The low voltage winding operates only on one voltage rating but different current rating based on the operating power rating.
| Switch Position | High Voltage | Low Voltage | ||||
| Voltage V | Current A @ 20 MVA | Current A @ 15 MVA | Voltage V | Current A @ 20 MVA | Current A @ 15 MVA | |
| 1 | 144900 | 79.7 | 59.8 | 13800 | 836.7 | 627.6 |
| 2 | 141450 | 81.6 | 61.2 | |||
| 3 | 138000 | 83.7 | 62.8 | |||
| 4 | 134550 | 85.8 | 64.4 | |||
| 5 | 131100 | 88.1 | 66.1 | |||
The transformer is designed to offer minimum losses across its internal circuit so that electricity can be delivered in an efficient manner. It is also part of international standards that electricity regulating devices like transformers have to have efficiency of 98.5 % or more.
This power transformer has impedance of 8.21 % at the rated power capacity with no load losses of 15.23 KW and load losses of 48.20 KW at given 15 MVA power rating.
This power transformer is cooled using a transformer special cooling system where instead of mineral oil, a synthetic ester or natural ester is used in the transformer cooling system. These systems are written as KNAN where K represents synthetic or natural ester, N represents natural convection and A represents atmospheric air.
This transformer is provided with two different cooling systems, each is designed to remove waste heat up to a specific level. A KNAN cooling system is designed to remove waste heat from the transformer when it is operating at 15 MVA power rating. Similarly a KNAF cooling system is integrated into the existing setup to remove waste heat of the transformer when it is operating at 20 MVA.

Transformer weight is a critical factor as the transformer has to be lifted, transported, and installed at the required location. The transformer was designed keeping in view the demand of low weight without compromising the transformer structure integrity and rigidity.
| Item | Weight |
| Tank Weight | 15700 lb |
| Equipment body load | 39500 lb |
| Oil Weight | 3155 gal |
| Temperature Rise of oil level | 65 K @ 15 MVA |
| Transport Weight | 71700 lb |
| Total Weight | 83800 lb |
This transformer was designed for reliability, safety and efficiency of its operation, so it is designed to comply with all concerned international standards like that of Canada national standard for electrical power transformer CSA C88. The transformer was designed, built, and inspected / tested as per international standard. The transformer passed the factory acceptance test and site acceptance test as per international standards before commissioning and operationalization. The transformer was designed and built with the best insulation system. This power transformer specifically offers an insulation level of LI650AC275 / LI110AC38 – LI110AC38.
At Daelim Transformer we can offer custom designed, regulation compliant power transformer solutions for critical energy infrastructure. The 138 kV 15/20 MVA transformer that was developed for the Canadian nation grid station demonstrates our technical excellence, quality control and ability to meet all international standards like that of CSA C88 and IEEE C57.12. This also shows our ability to deliver high efficiency products with minimal no load losses of 15.23 KW at 15 MVA power and with multiple cooling systems for reliable performance.
We have completed hundreds of projects for our clients all around the globe and if you have any question related to sizing, design, and delivery of electrical power transformers, then contact us.
Please Write your message, ask for price, we will reply you soon, thanks