Primary Voltage Ratings: 12.47 kV
Secondary Voltage Ratings: 4.16 kV
TYPE: Conservator type
Standards: IEEE Std. C57.12.00
Power Rating: 12/16/22 MVA
Cooling Type: ONAN/ONAF1/ONAF2
This is a custom design 22 MVA 3 phase power transformer with on load tap changer feature for easy and quick changing of transformer tap as per the electricity supply and electric load demand. The transformer is specifically designed and developed for the Taxes market in the USA so it complies with all international standards that are being followed in Taxes USA like IEEE C57.12.
The transformer offers three different power ratings with a base line power rating of 12 MVA. The transformer is also featured with the ability to have three different types of cooling system based on the power rating and electrical load attached to the transformer. The transformer can operate at 1000 meter altitude and work on 60 Hz frequency (standard for Taxes USA).
| Field | Value |
| Operation Condition | Out door |
| H.V BIL | 95 kV |
| L.V BIL | 60 kV |
| Operating Altitude | 1000 m |
| Power rating | 12/16/22 MVA |
| Rated Voltage | 12.47 ± 8 × 1.25% / 4.16 kV |
| Vector Group | Dyn1 |
| Frequency | 60 Hz |
| Number of Phases | 3 |
As this transformer is designed for Taxes national power grid system, it offers three different power ratings to deliver a comprehensive adaptability to different power outputs of national grid stations.
The transformer offer power rating of
In any given power rating, the transformer can offer different voltage and current combinations depending on the tap changer position. The 12 MVA work here as base line power rating and transformer impedance and load and no load losses are calculated based on this power rating.
This electrical transformer is designed with 12 KV (12470 Volts to be exact) as rated transformer voltage and with current of 1018 amps. The transformer offers 17 different tap positions that means 17 different voltages and current combinations to meet the ever changing grid supply and attached electrical load demand.
This is an oil type electrical transformer that uses mineral oil for transformer insulation and cooling purposes. The transformer uses about 21560 pounds of mineral oil for its insulation and cooling purpose. The transformer oil is kept inside a transformer tank that is designed and developed to hold oil and also facilitates the waste heat transfer.
To remove the waste heat, transformers use three different cooling systems where each system is designed to effectively remove waste heat of a specific power rating. The transformer has oil natural air natural, oil natural air forced system 1 and oil natural air forces system 2.
| Cooling Method | Rated Capacity |
| ONAN | 12 MVA |
| ONAF-1 | 16 MVA |
| ONAF-1 and ONAF-2 | 20 MVA |
Each part of the electrical transformer is very carefully designed and manufactured to deliver a compact design with minimum dimensions so that it is easy to transport and install the power transformer.
Weight of each major part of the electrical transformer is given below in pounds for better understanding of the transformer.
| Component | Weight (lbs) / Volume |
| Core and Coils | 33000 lbs |
| Tank and Fittings | 13200 lbs |
| Mineral Oil in Tank at 25°C | 21560 lbs |
| Total Weight | 62700 lbs |
| Weight of Transport (with oil) | 75240 lbs |
The power transformer delivered to Taxes USA can be used in different application in Taxes that includes:
The power transformer was designed and developed for Taxes USA and it follows all the international standards that are being followed in Taxes USA. The transformer had gone through complete factory acceptance testing and site acceptance testing before being commissioned on site. Some basic compliances are
Daelim transformers offer power transformers of any type, size, power capacity, and voltage range. Our transformers have all the standard features and we also offer customer design based on the client requirements. We deliver transformers that can compile with your national and mentioned international standard. We offer complete inhouse design, development, and testing of electrical transformers and we also provide our client with logistics planning and shipment services.
If you have any query about electrical transformers, contact our team and we will be happy to help you in your project.
Please Write your message, ask for price, we will reply you soon, thanks